In This Section |
Heat Recovery From Milk Cooling Systems
Table of Contents
IntroductionHeat energy is removed from milk during cooling. The heat energy can be 'dumped' from an air-cooled condenser, or all/or part of it can be transferred to water using a water-cooled condensing mechanism or a milk precooler. Water-cooled condensers and milk precoolers will reduce compressor running time. However, the greater energy (and dollar) savings usually come from displacing water heating energy costs. On most dairy farms the milk heat available can preheat more water than is required for nominal wash-up and sanitizing. The problem then is one of choosing a 'heat recovery system' that will provide only the warmed water needed on an individual farm -- with a reasonable payback. | Top of Page | Milk CoolingTo maintain milk quality, milk must be cooled from about 39° C (cow body temperature) to 3° C for safe storage. Milk is normally cooled by a refrigeration unit acting as a heat pump moving heat from a source (the milk) to a sink (air or water) using a carrier called a refrigerant (Freon gas). When the refrigerant changes state from a liquid to a gas in the evaporator (bulk milk tank) it absorbs heat from the milk. The compressor pressurizes the gaseous refrigerant. Under pressure the hot refrigerant will give up heat and revert to a liquid. The condenser provides a means for this heat to be removed. The heat can be released to the air within the milkhouse (or directed outside) or can be released to water depending on the type of condenser in place. The liquefied refrigerant then passes through an expansion valve mechanism causing a pressure drop. The refrigerant is now ready to absorb heat again. Figure 1. Refrigeration unit schematic.
| Top of Page | Heat RecoveryHeat recovery systems do not change the basic refrigeration cycle. They simply change the type or combination of condenser(s) used to remove heat from the refrigerant. Water-cooled condenser units can put all the heat from the refrigerant, which will include some of the compressor input energy, into water. This type of unit is efficient and generates about one litre of preheated water for every litre of milk cooled. This is often a much greater quantity of water than can be used effectively for normal wash-up and sanitizing operations in the milking area. | Top of Page | Water TemperatureThe average preheated water temperature from a watercooled condensing mechanism is likely to be in the 50° to 60° C range. Starting water temperatures for milking equipment washing (sanitizing) should be 75° C. Thus all preheated water used for sanitizing must be further heated using conventional energy sources. However, many auxiliary water uses such as: cow prepping, calf feeding, employee showering, can use the preheated water without further heating. | Top of Page | Preheated Water UsageBefore investing in any type of heat recovery equipment, potential preheated water usage should be estimated. Dumping preheated water as a means of heat disposal may not be prudent - especially if potable water supply is limited. Unfortunately no reliable warm (hot) water use guidelines are available. Reported average uses vary from 4 to 14 L/cow per day, with most below 10. Except when significant warm water uses exist in addition to the normal equipment/facilities wash-up (sanitizing), it is not likely that more than one-half of the milk heat can be used effectively for water preheating. Fortunately equipment is available to permit recovery of one-half or less of the milk heat efficiently. The equipment choice will vary with the size of the refrigeration system required or in place for the specific dairy operation. Milk heat is a reliable source, occurring every time the cows are milked. It must be used as produced or stored temporarily because the milk must be cooled quickly to maintain quality standards. Thus it is not a constant source for space heating (i.e. the calf nursery) and is not required on a year round basis for that type of application. Pit floor heating with warmed water can also be installed in new milking parlors. If automatic prep stalls are used with parlors, the warmed water use rate might warrant total milk heat recovery. No common external uses are evident or economically viable at this time for most Ontario dairy operations. If energy prices increase significantly, the possibility exists to pipe preheated water to the hot water heater in the residence. Warming the swimming pool is another potential use - but it is limited to very large milking herds. Figure 2. A conventional air-cooled condensing unit and compressor discharging milk heat into air.
| Top of Page | Estimating Present Hot Water UsageBy accurately estimating the quantity of hot (75° to 77° C) or warmed (50° to 60° C) water that can be used effectively, local dairy equipment suppliers should be able to recommend the most cost effective heat recovery system for individual dairy operations. If a conventional water heater is in place, a water meter in the cold supply line is the most accurate rate test. For existing electric water heaters two other estimating techniques are available. One is to install a temporary kilowatt hour meter. Energy consumption should be recorded for at least two and preferably about ten days. For heaters in cold locations providing 75 to 77° C water assume about 10 L of hot water for each kWh of energy input. Example: The electric water heater uses 360 kWh over 12 days. Average energy use rate will be 30 kwh/day. Approximate hot water usage is: 30 x 10 = 300 L/day. If a kilowatthour meter is not available, a recording amp meter or a cumulative timer attached to the water heater circuit can provide average daily water heater 'on-time'. After checking the heating element rating, Table 1 can be used to estimate the hot water use rate.
* Based on both upper and lower elements being the same wattage with only one energized - which is the common arrangement in all newer electric water heaters. ** Based on 10L/kWh which assumes a standby heat loss of approx. 33%. If testing occurs during hot weather the hot water use values can be increased by 10 to 15%. | Top of Page | Heat Recovery Systems
| Top of Page | EconomicsThe economic attractiveness of heat recovery from milk must be based primarily on purchased energy displacement for water heating. While water-cooled condensers, desuperheaters and precoolers will reduce compressor running time, the resultant energy savings are not well documented. Properly sized and well maintained conventional aircooled condensers systems are generally doing an adequate job of lowering milk temperature quickly enough to maintain quality standards. However, when refrigeration system changes or upgrades are required heat recovery systems should be considered to reduce water heating costs. Figure 5. Potential energy (dollar) savings by transferring milk heat to water - based on daily milk production and warmed water usage.
Figure 5 illustrates by examples the range of opportunity for capital recovery of heat recovery equipment for most dairy operations in Ontario. Example "A" is for a common (35 milking cow) dairy unit producing 750 L of milk a day and using hot water at the rate of 250 L/d (7 L/cow/d). Only 33% of the milk heat can be used to preheat that amount of hot water. With electricity costing $0.05/kWh as the water heating alternative energy the annual savings potential is $210. The present cost for a small (190 L) add-on 'desuperheater' would be about $1400. Thus the capital cost recovery is not particularly attractive at approximately seven years simple payback without interest. The additional heating of all the water used for sanitizing in this example is approximately 50% of previous water heating costs. In contrast, a much larger dairy operation, Example "B" producing 2150 L of milk a day and having a high percentage (70%) warm water to milk usage, has an excellent opportunity to benefit from milk heat recovery. With electrical water heating energy at $0.05/kWh the annual savings potential is $1300. This would permit an expenditure of $3900 for heat recovery equipment and provide simple payback in three years. A significant portion of the warmed (50° C) water could be used directly in this operation for showering, facility washdown etc. | Top of Page | Summary
ReferencesWinfield, R.G. and W.A. Gee, 1983. Energy recovery from milk - Can the heat be used effectively? Report for the Agricultural Energy Centre, Ontario Ministries of Agriculture and Food and Energy. Mastitis control and prevention committee, 1982. Guidelines for the installation and operation of milking and milk handling equipment. Special report, Animal Production Division, Agriculture Canada, Ottawa, Ontario, KIA 0C5. | Top of Page | For more information:Toll Free: 1-877-424-1300 Local: (519) 826-4047 E-mail: ag.info.omafra@ontario.ca |
||||||||||||||||||||||||||||||||||||||||||||||||
This site is maintained
by the Government of Ontario
Queen's
Printer for Ontario
Last Modified: